What is the function of battery used in Micrologic Trip unit.
The battery inside the Micrologic keeps the Clock and Calendar maintained when the Control Supply has failed. This battery also allows the testing...
Is it possible to use Altivar 71 Drive for control of the Synchronous Motor.
Yes, Altivar 71 Drive can be used for control of the Synchronous Motor.  Note:   1. The Drive should be programmed for Open-Loop Control.   2. De-rate...
What is the maximum motor cable length allowed between the Sinus Filter and Altivar 71 Drive.
The maximum motor cable length allowed between the Sinus Filter and Altivar 71 Drive is 1000 Meters.
What is the accuracy of the Premium PLC CPU real time clock.
Real time clock accuracy: Accuracy of the real time clock is one second (%SW50) +/- 200ms. Resolution of the real time clock is one second (%SW50)...
Do Unity Pro and Unity Application Generator (UAG) have separate licenses.
Yes, Unity Pro and UAG have separate licenses.   During installation of UAG, it detects the existing Unity Pro versions on your PC/Laptop and it will...
What is the execution time and memory consumption of the PIDFF instruction in Unity Pro Quantum platform.
It has been observed that the maximum time taken for executing PIDFF instruction is around 50 microseconds on Unity Pro Quantum platform.   Regarding...
What is the minimum rating of the Motor that can be used with the Altivar 31/61/71 Range of Drives.
The motor current should not be less than 0.2 times the nominal Drive current when the motor is driven by Altivar 31/61/71 Drives, for thermal protection....
Is it possible to use TeSys GV2 and TeSys GV3 Range MPCB in DC applications.
The TeSys GV2 and TeSys GV3 range MPCB can be used in DC applications as per their technical specifications.  Refer the below wiring connection for...
Is it possible to give continuous supply to the Shunt Trip (MX) coil of Compact NSX circuit breaker?
Yes, you can keep the supply ON continuously for the Shunt Trip coil (MX) of Compact NSX Circuit Breaker as new technology permits this without damaging...
Can I use an undervoltage release (MN type) for C60 on a 60 Hz system.
Yes, the MN undervoltage release for C60 circuit-breakers can be used on a 60 Hz system. The C60 range is now obsolete. The current range, the Acti9...