When programming the ATS48 analog output for motor current scaled?

Issue:

When programming the ATS48 analog output for motor current, AO=OCr, is the scaling parameter ASC a percentage based on the motor current parameter In or based on the nameplate current rating of the specific ATS48?

Product Line:

Altistart 48, ATS48

Environment:

All

Cause:

Programming the ATS48 analog output for motor current.

Resolution:

It is based on the motor current programmed into In. It is adjustable from 50 to 500% of the In value.